Caterpillar CCM to Modbus Panel (CCMM)

Caterpillar CCM to Modbus Conversion Panel (CCMM)

Converts Caterpillar CCM to Modbus RTU or ASCII Protocol

APTView SCADA Control Panel HMI

 

Caterpillar CCM to Modbus Conversion Communications Panel (CCMM) - integrates Caterpillar CCM and converts output to RS-485 w/ Modbus RTU or ASCII protocol. Caterpillar CCM to Modbus Protocol Conversion Panel Communications Module

The APT Caterpillar CCM to Modbus (CCMM) Communications panel integrates Caterpillar CCM and converts its output to RS-485 port with Modbus RTU or ASCII protocol. Modbus RTU protocol allows for easy integration into customers SCADA, DSC or other computerized monitoring systems.This is a wall mounted panel and is very easy to install. No special tools or connectors are required. One CCMM with one CCM will monitor one (1) EUI engine and one (1) EMCPII+ panel or two (2) EMCPII+ panels.

  • Fully Integrated NEMA 1 Wall-Mounted Panel
  • Standard Terminal Points for Field Connected 120VAC and 24VDC Power, CAT Data Link, and RS-485 Connections
  • Jumper Selectable 2 Wire or 4 Wire RS-485 Connection
  • 16 Additional 24VDC Inputs for Monitoring Additional Field Devices such as Fuel, Oil and Coolant Levels, Spill Switches, Circuit Breaker Positions, etc.
  • 16 Additional 24VDC Digital Outputs for Controlling Louvers, Circuit Breakers, Start/Stop, etc.
  • All 24VDC Inputs and Outputs are Readable and Writeable Via Modbus Port
  • Custom Register Mapping is Available

PDF Icon APT Caterpillar CCM to Modbus Conversion Panel (CCMM) Spec Sheet